Types of Receptacles for Psychiatric
Wards
Q. We had an inspection on our
psychiatric ward and the question came
up about what type of receptacles are
approved in this type of environment...
In the patient rooms we installed a
special cover with a tamper proof screw
over the receptacle which was accepted.
They are asking for is GFCI receptacles
in the hallways of this ward. To my
understanding, GFCI receptacles are for
wet locations and devices exposed to the
elements. My question is what type if
any receptacles are accepted in this
type of area. As I said before the
receptacles that are in the patient
rooms are covered. The hallways are
monitored by staff but the patients
still have access to them.
A. The first part of the answer
is: "What does your state require that is
different than what is required by NFPA
Codes?
The second part of the answer has
to be: "When was your facility constructed
and what codes did they use at that
time? Has it been renovated in that
specific area since then?"
In my opinion - having maintained
inpatient care areas for all age groups
of patients who have psychiatric, mental
health issues and/or behavioral problems,
I have found that the best approach when
providing electrical receptacles in
these areas is to provide outlets that
provide both tamper resistance and GFCI
protection. Patients can and will find
ways to harm themselves given the
opportunity to do so. I have never found
tamper resistant covers to provide much
protection. It has been my thoughts that the
cost of the outlets that provided both
tamper and GFCI were far less than the
cost associated with handling an event
if a patient hurts themselves.
OK now we can provide some general code
answers!
Let's start with Psychiatric Hospital -
A building used exclusively for the
psychiatric care, on a 24-hour basis, of
four or more inpatients.
The 2008 edition of the NEC states
the following:
517.18 General Care Areas.
(A) Patient Bed Location. Each
patient bed location shall be supplied
by at least two branch circuits, one
from the emergency system and one from
the normal system. All branch circuits
from the normal system shall originate
in the same panelboard.
Exception No. 1: Branch circuits
serving only special-purpose outlets or
receptacles, such as portable X-ray
outlets, shall not be required to be
served from the same distribution panel
or panels.
Exception No. 2: Requirements of
517.18(A) shall not apply to patient bed
locations in clinics, medical and dental
offices, and outpatient facilities;
psychiatric, substance abuse, and
rehabilitation hospitals; sleeping rooms
of nursing homes and limited care
facilities meeting the requirements of
517.10(B)(2).
Exception No. 3: A general care
patient bed location served from two
separate transfer switches on the
emergency system shall not be required
to have circuits from the normal system.
(B) Patient Bed Location Receptacles.
Each patient bed location shall be
provided with a minimum of four
receptacles. They shall be permitted to
be of the single or duplex types or a
combination of both. All receptacles,
whether four or more, shall be listed
“hospital grade” and so identified. The
grounding terminal of each receptacle
shall be connected to an insulated
copper equipment grounding conductor
sized in accordance with Table 250.122.
Exception No. 1: The requirements
of 517.18(B) shall not apply to
psychiatric, substance abuse, and
rehabilitation hospitals meeting the
requirements of 517.10(B)(2).
Exception No. 2: Psychiatric
security rooms shall not be required to
have receptacle outlets installed in the
room.
FPN: It is not intended that
there be a total, immediate replacement
of existing non–hospital grade
receptacles. It is intended, however,
that non–hospital grade receptacles be
replaced with hospital grade receptacles
upon modification of use, renovation, or
as existing receptacles need
replacement.
------------------------------------------------------
OK so we now know that psychiatric rooms
do not have to have receptacles per the
2008 edition of the NEC but if they are
installed they need to be hospital grade
devices. The requirement that stated
the outlets or covers had to be
tamper resistant is no longer in this
code section, nor was it in the 2005
edition - but may well exist in a state
code.
------------------------------------------------------
NFPA 99 states the following:
4.3.2.2.6.2 Minimum Number of
Receptacles. The number of
receptacles shall be determined by the
intended use of the patient care areas
in accordance with 4.3.2.2.6.2(A)
through 4.3.2.2.6.2(D).
(A) Receptacles for Patient Bed
Locations in General Care Areas.
Each patient bed location shall be
provided with a minimum of four
receptacles (or two duplex receptacles).
(B) Receptacles for Patient Bed
Locations in Critical Care Areas.
Each patient bed location shall be
provided with a minimum of six
receptacles (or three duplex
receptacles).
(C) Receptacles for Bathrooms or
Toilets. Receptacles shall not be
required in bathrooms or toilet rooms.
(D) Receptacles for Special Areas.
Receptacles shall not be required in
areas where medical requirements mandate
otherwise (e.g., certain psychiatric,
pediatric, or hydrotherapy areas).
II. Wiring and Protection
517.10 Applicability.
(A) Applicability. Part II shall
apply to patient care areas of all
health care facilities.
(B) Not Covered. Part II shall
not apply to the following:
(1) Business offices, corridors,
waiting rooms, and the like in clinics,
medical and dental offices, and
outpatient facilities
Selected Receptacles. A minimum
number of electrical receptacles to
accommodate appliances ordinarily
required for local tasks or likely to be
used in patient care emergencies.
Psychiatric Hospital. A building
used exclusively for the psychiatric
care, on a 24-hour basis, of four or
more inpatients.
------------------------------------------------------
I find no requirements for having GFCI
outlets for corridors. This may be a
state requirement.
------------------------------------------------------
Wet Procedure Locations. Those
spaces within patient care areas where a
procedure is performed and that are
normally subject to wet conditions while
patients are present. These include
standing fluids on the floor or
drenching of the work area, either of
which condition is intimate to the
patient or staff. Routine housekeeping
procedures and incidental spillage of
liquids do not define a wet location.
517.20 Wet Procedure Locations.
(A) Receptacles and Fixed Equipment.
All receptacles and fixed equipment
within the area of the wet procedure
location shall have ground-fault
circuit-interrupter protection for
personnel if interruption of power under
fault conditions can be tolerated, or be
served by an isolated power system if
such interruption cannot be tolerated.
Exception: Branch circuits
supplying only listed, fixed,
therapeutic and diagnostic equipment
shall be permitted to be supplied from a
grounded service, single- or 3-phase
system, provided that
(a) Wiring for grounded and
isolated circuits does not occupy the
same raceway, and
(b) All conductive surfaces of
the equipment are connected to an
equipment grounding conductor.
(B) Isolated Power Systems. Where
an isolated power system is utilized,
the isolated power equipment shall be
listed as isolated power equipment, and
the isolated power system shall be
designed and installed in accordance
with 517.160.
FPN: For requirements for installation
of therapeutic pools and tubs, see Part
VI of Article 680.
517.21 Ground-Fault
Circuit-Interrupter Protection for
Personnel.
Ground-fault circuit-interrupter
protection for personnel shall not be
required for receptacles installed in
those critical care areas where the
toilet and basin are installed within
the patient room.
Patient Care Area. Any portion of
a health care facility wherein patients
are intended to be examined or treated.
Areas of a health care facility in which
patient care is administered are
classified as general care areas or
critical care areas. The governing body
of the facility designates these areas
in accordance with the type of patient
care anticipated and with the following
definitions of the area classification.
FPN: Business offices, corridors,
lounges, day rooms, dining rooms, or
similar areas typically are not
classified as patient care areas.