Relocation
Q. "What do
the new EPA regulations say about the
“relocation” of an existing generator to
a new location? Are they even covered by
the new regs?" (40 CFR 60.4208)
A. Under the
general provisions (60.14(e)(6)) a
relocation of an "existing" engine
(i.e., an engine that has already been
installed and operated) would not result
in the existing engine becoming a new
engine upon relocation unless the
relocation also included changes such
that the engine was reconstructed (See
60.15 for the reconstruction
provisions). According to Table 8 of
Subpart IIII, Section 60.14(e)(6) is an
applicable section. I don't see any
mention of the term "relocation" in
subpart IIII so I assume the subpart
relies solely on Section 60.14(e)(6) of
the general provisions with regard to
relocations.
|
|
|