30 Percent Rule
Q. I am
looking for some clarification on the 30
percent rule for the monthly load
testing of my generators. The generator
in question is a 60 KW with an amp
rating of 208.2. This generator does not
have a KW output reading so we use the
amp output for determining the 30
percent. ( 63 amps per leg at 208
voltage ) During one of the tests the
amp readings where (65 , 40 , 110) which
has one leg under 30 percent. If you
look at the overall output of the
generator it is 20.6 KW and I only need
18.1 KW to meet the 30 percent. Thank
you for any help you could give me.
A. My
opinion is that you are over the 30% at
20.6kw (even with one leg being severely
out of balance…and under the average).
As you know NFPA 110 doesn’t state how
the kW is to be computed, but normal
practice would be to “average” the legs.
Note that I cannot
speak for the NFPA nor render an opinion
on their behalf even though I am a
member of the Technical Committee
responsible for NFPA 110.