Q. Do you
know where in the code it states that a
generator should be readily accessible?
We have a contractor that does not want
to put in a generator platform. The
genset has a belly tank that is about 4’
high.
A. NFPA 110,
5.6.3.4 states: “The instruments
required in 5.6.3.3(1) through
5.6.3.3(4) shall be placed on an
enclosed panel, located din proximity to
or on the energy converter, in a
location that allows maintenance
personnel to observe them readily. The
enclosed panel shall be mounted by means
of anti-shock vibration mountings if
mounted on the energy converter.” It
is standard practice to erect a platform
or catwalk so the control panel is
visible. See pictures below….this one
has a 5000 gallon belly tank.


|
|
|