Air Handler
Shutdown
Q. I would
like to know if you can articulate the
EC 5.40 elements of performance on the
following matter. Is it a true statement
that in order to verify that the shut
down device(s) works you must shut the
air handler down. I don’t see this
statement contained in EC5.40 items # 1
and 15. I also looked up NFPA 90A and it
doesn’t reference that the unit must be
shut down in order to determine if the
automatic shutdown devices work. Can you
please expand on this matter? I
referenced item # 6.4.2 an 6.4.4.2.1. in
NFPA 90A.
A. The NFPA
code section reference reads "all
automatic shutdown devices shall be
tested annually". A reasonable person
would consider that to include smoke
detectors, relays and other controls. To
me, it does not include HVAC fan motors.
Be that as it may, the way we wire life
safety devices around here you would
have to jump something out electrically
to avoid shutting down the HVAC- in
other words if you have a "hand"
position on a motor control circuit, it
will be overriden by life safety
signals. By jumping it out, you are not
completely testing the controls. You
could have a welded relay contact and
never know it, for example, if you jump
that relay out to keep the fan online.
Later in that code
book, the acceptance testing section
states "Acceptance tests of fire
protection devices in air-conditioning
and ventilating systems shall, as far as
practicable, be performed under normal
operating conditions."
To me, that is the
best way to test something - "end to
end" is what I call it. You would be
amazed what can be inadvertently
overlooked when you do anything less
than a "real" test. As much of a PITA as
a real test can be, it is usually worth
doing.
Hope this helps.
John M. Kramer PE