Q. Hey Dan,
What is the criteria for testing stored
systems? We have a 125kva and a 20kva
UPS System that protects our servers for
the hospital. This system is acting as a
bridge until our generators come online
and transfer to emergency during a power
failure. How often do we test them and
at what % according to Joint Commission
standards?
A. They only
have to be tested according to
manufacturer’s standards. They are not
“SEPSS” which requires testing as per
NFPA 111 and the JCAHO 7.40 standards. A
“UPS” is not an “SEPSS” unless it is
used as a separate “alternate source of
power” and NOT downstream from a
generator. Dan
More information on
SEPSS can be found in our
archive section.